| AC
power supply |
DC
power supply |
 |
Rated
voltage |
100-240VAC |
24VDC |
| Permissible range
of voltage |
100-240VAC±10% |
24VDC±10% |
Permissible
momentary
power failure |
Within
20ms |
Within
1ms |
Power consumption
(Maximum rating) |
40VA
or less |
12W
or less |
| Inrush current |
For
100VAC: 16A, 6ms
For 200VAC: 32A, 7ms |
30A,
1ms |
| Withstand voltage |
AC
external terminals to
FG: 1500VAC, 1 minute |
DC
external terminals to
FG: 500VAC, 1 minute |
| Insulation
resistance |
500VDC,
10MΩ or above |
 |
Ambient
temperature |
0ºC
to +50ºC |
| Storage ambient
temperature |
-10ºC
to +60ºC |
| Ambient humidity |
85%
RH or less (Avoid condensation) |
| Solvent resistance |
No
cutting oil or organic solvent clung to the unit |
| Atmosphere |
No
corrosive gas or conductive dust |
 |
Vibration
resistance |
Vibration
frequency: 10 to 150Hz, Acceleration: 9.8m/s2
Single amplitude: 0.075mm, X, Y, Z: 3 directions for
one hour |
| Shock resistance |
Pulse
shape: half sine wave
Peak acceleration: 147m/s2, X, Y, Z: 3
directions six times each |
 |
Noise immunity |
1500Vp-p
(pulse width 1µs, rise time: 1ns) |
Anti-static
electricity
discharge |
Conforming
to IEC61000-4-2, contact: 6kV, air: 8kV |
 |
Grounding |
Grounding
resistance: less than 100Ω |
| Structure |
Degree
of protection: rear case: IP20
Form: in a single body
Mounting method: Panel flush mounting |
| Cooling system |
Natural
cooling |
| Mass (kg) |
Unit:
approx. 1.6 |
| Dimensions W x H x
D (mm) |
Main
unit only: 315 x 214.6 x 51.7
When option unit UG30A-ROS is installed: 315 x 214.6
x 72.7 |
| Case
color |
Black
(Munsell N2.0) |
| Case
material |
PC/PS
resin |