Item
|
Explanation
|
Remarks
|
Related function code
|
| Output
frequency |
Setting
range |
Maximum frequency |
25
to 120Hz |
|
F03 |
| Base frequency |
25
to 120Hz |
|
F04 |
| Starting
frequency |
0.1
to 60.0Hz |
|
F23 |
| Carrier
frequency |
•
0.75 to 15kHz (200V/400V:0.75 to 22kW)
• 0.75 to 10kHz (200V/400V:30 to 75kW)
• 0.75 to 6kHz (200V/400V:90 to 500kW) |
The carrier
frequency may drop automatically according to the ambient
temperature or output current to protect the inverter. This
protective operation can be canceled by function code H98. |
F26
F27
H98 |
| Accuracy
(Stability) |
•
Analog setting: ±0.2% of maximum frequency (at 25±10°C)
• Keypad setting: ±0.01% of maximum frequency (at -10
to +50°C) |
|
|
| Setting
resolution |
•
Analog setting: 1/1000 of maximum frequency (ex. 0.06Hz at
60Hz, 0.12Hz at 120Hz)
• Keypad setting: 0.01Hz (99.99Hz or less), 0.1Hz
(100.0Hz or more)
• Link setting: Selectable from 2 types
•1/20000 of maximum frequency (ex. 0.003Hz at
60Hz, 0.006Hz at 120Hz)
•0.01Hz (fixed) |
Setting
with , keys. |
|
| Control |
Control
method |
V/f
control |
|
|
Voltage/freq.
characteristic
|
Possible
to set output voltage at base frequency and at maximum
output frequency
(common spec.). AVR control can be turned ON or OFF. |
Three-phase
200V: 80 to 240V
Three-phase 400V: 160 to 500V |
F03toF05 |
|
(Non-linear V/f setting)
|
1
point (Arbitrary voltage and frequency can be set.) |
Three-phase
200V: 0 to 240V/0 to 120Hz
Three-phase 400V: 0 to 500V/0 to 120Hz |
H50,H51 |
|
|
Torque
boost can be set with the function code F09. |
Set when 0,
1, 3, or 4 is selected at F37. |
F09, F37 |
|
(Load selection)
|
Select
application load type with the function code F37.
0: Variable torque load 1: Variable torque load (for high
starting torque) 2: Auto-torque boost
3: Auto-energy-saving operation (variable torque load in
acceleration/deceleration)
4: Auto-energy-saving operation (variable torque load (for
high starting torque) for acceleration/deceleration)
5: Auto-energy-saving operation (auto-torque boost in
acceleration/deceleration) |
|
F09, F37 |
| Starting
torque |
50%
or over |
|
|
| Start/stop |
Keypad
operation |
Start
(FWD/REV) and stop with , keys |
Keypad
(standard) |
F02 |
Start and
stop with / , keys |
Multi-function
keypad (optional) |
F02 |
External
signals (7 digital inputs): Forward (reverse) rotation, stop
command (capable of 3-wire
operation), second operation command, coast-to-stop command,
external alarm, alarm reset, etc. |
|
E01toE05
E98,E99 |
| Link
operation: Operation through RS485 communication and Field
Bus communication (option) |
|
H30, y98 |
| Operation
command switch: Remote/local switch, link switch, second
operation command switch |
|
|
| Frequency
setting |
Keypad
operation: Can be set with
, keys |
|
F01, C30 |
| External
potentiometer: Can be set with the external resistor (1 to
5k?, 1/2W) |
Connected
to analog input terminals 13, 12,
11. A separate variable resistor is necessary. |
|
| Analog
input |
Can be set
with external voltage/current input.
0 to +10V DC (0 to +5V DC)/0 to 100% (terminal 12, V2)
4 to 20mA DC/0 to 100% (terminal C1) |
0 to +5V
DC:change (200%) in analog
input gain setting. +1 to +5V DC:adjustable
with bias/analog input gain |
F18, C50,
C32toC34, C37toC39, C42toC44 |
| Multistep
frequency: Selectable from 8 steps (step 0 to 7) |
|
C05toC11 |
| UP/DOWN
operation: The frequency rises or lowers while the digital
input signal is turned on. |
|
F01,
C30 |
| Link
operation: Can be set with RS485 communications and field
bus communications (option). |
|
H30,
y98 |
Frequency
setting change: Two types of frequency settings can be
switched with an external signal (digital input).
Changeover between remote and local (keypad operation) or
frequency setup through communication is also possible. |
|
F01,
C30 |
Auxiliary
frequency setting: Inputs at terminal 12, C1 or V2 can be
added to the main setting
as auxiliary frequency settings. |
|
E61toE63 |
Reverse
action: The digital input signal and function code setting
sets or switches between
the forward and reverse actions.
• +10 to 0V DC/0 to 100%(Terminal 12, V2) • 20
to 4mA DC/0 to 100%(Terminal C1) |
|
C53 |
Acceleration
/ deceleration
time |
0
to 3600s
• Acceleration and deceleration pattern can be
selected from 4 types: Linear,
S-curve (weak), S-curve (strong), Curve (constant output
max. capacity).
• Shutoff of the operation command coasts the motor to
decelerate and stop. |
|
F07, F08
H07
H11 |
| Frequency
limiter |
High
and low limiters can be set (setting range: 0 to 120Hz) |
Selection
can be made between continuation of operation and
stopping at frequencies equal to or smaller than the lower
limit. |
F15, F16
H63 |
| Bias
frequency |
Bias
of set frequency and PID command can be set in the range
between 0 and ±100%. |
|
F18,
C50toC52 |
| Gain
for frequency setting |
The
analog input gain can be set in the range from 0 to 200%. |
Voltage
signals (terminal 12, V2) and current
signal (terminal C1) can be set independently. |
C32,C34,
C37
C39,C42,
C44 |
| Jump
frequency setting |
3
operation points and their common jump hysteresis width (0
to 30Hz) can be set. |
|
C01toC04 |
Restart
after momentary
power failure |
•The
inverter restarts upon recovery from power failure without
stopping the motor.
• In the "operation continuation mode,"
recovery of the power supply is waited for while the output
frequency slightly drops.
• Selection can be made among starting at 0Hz,
starting at the frequency immediately before the momentary
power failure,
and starting at a set frequency for the starting method
after power recovery. |
|
F14
H13toH16,
H92,H93 |
| Current
limit |
Keeps
the current under the preset value during operation. |
|
F43,F44 |
| Line/inverter
switching |
•Line/inverter
switching (starting at line frequency) can be made with a
digital input signal (SW50, SW60).
• A built-in line/inverter switching sequence performs
sequence control with a digital input signal (ISW50, ISW60)
to
output a signal (SW88, SW52-1, SW52-2) for controlling an
external magnetic contactor (MC). As a built-in
sequence, two types can be selected, including the one
switching automatically to the line upon an inverter alarm. |
|
J22 |
| PID
control |
Capable
of PID regulator control for process |
|
E61toE63
J01toJ06
J10toJ19 |
Process
commands
• Key operation (UP and DOWN keys):0 to 100%
• Analog input (terminal 12, V2):0 to +10V DC/0 to
100%
• Analog input (terminal C1):4 to 20mA DC/0 to 100%
• UP/DOWN (digital input):0 to 100%
• Communication (RS485, bus option):0 to 20,000/0 to
100 |