| > Fuji
Products Center >
Fuji Inverters > FRENIC-ECO
> Standard specifications |
|
|
Item
|
Specifications
|
Type (FRN  F1S-2A) |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
75 |
90 |
110 |
| Applicable
motor rating [kW] (*1) |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
75 |
90 |
110 |
| Output
ratings |
Rated
capacity[kVA] (*2) |
1.6 |
2.6 |
3.8 |
6.2 |
8.3 |
11 |
16 |
21 |
25 |
30 |
40 |
49 |
59 |
75 |
102 |
121 |
146 |
| Rated
voltage[V] (*3) |
Three-phase,
200V/50Hz, 200, 220, 230, 240V/60Hz (With AVR function) |
| Rated
current[A] (*4) |
4.2 |
7.0 |
10 |
16.5 |
22.5 |
29 |
42 |
55 |
68 |
80 |
107 |
130 |
156 |
198 |
270 |
320 |
384 |
| Overload
capability |
120% of
rated current for 1min |
| Rated
frequency[Hz] |
50, 60Hz |
| Input
ratings |
Phases,
voltage,
frequency |
Main power
supply |
Three-phase,
200 to 240V, 50/60Hz |
Three-phase,
200 to 220V/50Hz
Three-phase, 200 to 230V/60Hz |
Auxiliary control
power input |
Single-phase,
200 to 240V, 50/60Hz |
Single-phase,
200 to 220V/50Hz
Single-phase, 200 to 230V/60Hz |
| Voltage/frequency
variations |
Voltage:
+10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency:
+5 to -5% |
| Rated
current[A] (*5) |
(with DCR) |
3.2 |
6.1 |
8.9 |
15.0 |
21.1 |
28.8 |
42.2 |
57.6 |
71.0 |
84.4 |
114 |
138 |
167 |
203 |
282 |
334 |
410 |
| (without DCR) |
5.3 |
9.5 |
13.2 |
22.2 |
31.5 |
42.7 |
60.7 |
80.1 |
97.0 |
112 |
151 |
185 |
225 |
270 |
-
|
-
|
-
|
| Required
power supply capacity[kVA] (*6) |
1.2 |
2.2 |
3.1 |
5.3 |
7.4 |
10 |
15 |
20 |
25 |
30 |
40 |
48 |
58 |
71 |
98 |
116 |
142 |
| Braking |
Torque[%]
(*7) |
20
|
10 to15
|
| DC injection
braking |
Starting
frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s,
Braking level: 0 to 60% |
| DC
REACTOR(DCR) |
Option |
Standard |
| Applicable safety standards |
UL508C, C22.2No.14,
EN50178:1997(Applying) |
| Enclosure(IEC60529) |
IP20 UL
close type |
IP00 UL open
type |
| Cooling
method |
Natural
cooling |
Fan cooling |
| Weight /
Mass[kg] |
|
|
|
|
3.3 |
5.6 |
5.6 |
6.6 |
9.3 |
9.5 |
11.7 |
23 |
31 |
34 |
41 |
|
|
| (*1) |
Fuji's 4-pole standard motor |
| (*2) |
Rated capacity is calculated by assuming
the output rated voltage as 220V for three-phase 200V
series. |
| (*3) |
Output voltage cannot exceed the power
supply voltage. |
| (*4) |
When setting the carrier frequency (F26)
to 1 kHz, reduce the load to 80% of its rated value. |
| (*5) |
Calculated under Fuji-specified
conditions. |
| (*6) |
Obtained when a DC REACTOR is used. |
| (*7) |
Average braking torque without optional
braking resistor (Varies with the efficiency of the motor.) |
| (*8) |
Voltage unbalance [%] =(Max. voltage [V] -
Min. voltage [V])/(Three-phase average voltage [V])x 67
(IEC61800-3(5.2.3)) |
| |
If this value is 2 to 3%, use an AC
REACTOR. |
|
|
|
|
|
Item
|
Specifications
|
Type
(FRN  F1S-4A) |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
| Applicable
motor rating [kW](*1) |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
| Output
ratings |
Rated
capacity[kVA](*2) |
1.9 |
2.8 |
4.1 |
6.8 |
9.5 |
12 |
17 |
22 |
28 |
33 |
44 |
54 |
64 |
77 |
| Rated
voltage[V](*3) |
Three-phase,
380, 400V/50Hz, 380, 400, 440, 460V/60Hz (with AVR function) |
| Rated
current[A](*4) |
2.5 |
3.7 |
5.5 |
9.0 |
12.5 |
16.5 |
23 |
30 |
37 |
44 |
58 |
71 |
84 |
102 |
| Overload
capability |
120% of
rated current for 1min |
| Rated
frequency[Hz] |
50, 60Hz |
| Input
ratings |
Phases,
voltage,
frequency |
Main power supply |
Three-phase,
380 to 480V, 50/60Hz |
Three-phase,
380 to 440V/50Hz
Three-phase, 380 to 480V/60Hz |
Auxiliary control
power input |
Single-phase,
380 to 480V, 50/60Hz |
Single-phase,
380 to 440V/50Hz
Single-phase, 380 to 480V/60Hz |
| Voltage/frequency
variations |
Voltage:
+10 to -15% (Voltage unbalance: 2% or less(*8)), Frequency:
+5 to -5% |
| Rated
current[A](*5) |
(with DCR) |
1.6 |
3.0 |
4.5 |
7.5 |
10.6 |
14.4 |
21.1 |
28.8 |
35.5 |
42.2 |
57.0 |
68.5 |
83.2 |
102 |
| (without DCR) |
3.1 |
5.9 |
8.2 |
13.0 |
17.3 |
23.2 |
33.0 |
43.8 |
52.3 |
60.6 |
77.9 |
94.3 |
114 |
140 |
| Required
power supply capacity[kVA](*6) |
1.2 |
2.2 |
3.1 |
5.3 |
7.4 |
10 |
15 |
20 |
25 |
30 |
40 |
48 |
58 |
71 |
Braking
|
Torque[%](*7) |
20
|
10 to 15
|
| DC injection
braking |
Starting
frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s,
Braking level: 0 to 60% |
| DC
REACTOR(DCR) |
Option |
| Applicable safety standards |
UL508C, C22.2No.14,
EN50178:1997(Applying) |
| Enclosure
(IEC60529) |
IP20 UL
close type |
IP00 UL open
type |
| Cooling
method |
Natural
cooling |
Fan cooling |
| Weight / Mass[kg] |
|
|
|
|
3.3 |
5.6 |
5.7 |
6.6 |
9.2 |
10.3 |
11.7 |
23 |
23 |
30 |
| (*1) |
Fuji's 4-pole standard motor |
| (*2) |
Rated capacity is calculated by assuming
the output rated voltage as 440V for three-phase 400V
series. |
| (*3) |
Output voltage cannot exceed the power
supply voltage. |
| (*4) |
When setting the carrier frequency (F26)
to 1 kHz, reduce the load to 80% of its rated value. |
| (*5) |
Calculated under Fuji-specified
conditions. |
| (*6) |
Obtained when a DC REACTOR is used. |
| (*7) |
Average braking torque without optional
braking resistor (Varies with the efficiency of the motor.) |
| (*8) |
Voltage unbalance [%] =(Max. voltage [V] -
Min. voltage [V])/(Three-phase average voltage [V])x 67
(IEC61800-3(5.2.3)) |
| |
If this value is 2 to 3%, use an AC
REACTOR. |
|
|
|
|
Item
|
Specifications
|
Type (FRN  F1S-4A) |
75 |
90 |
110 |
132 |
160 |
200 |
220 |
280 |
315 |
355 |
400 |
450 |
500 |
| Applicable
motor rating[kW](*1) |
75 |
90 |
110 |
132 |
160 |
200 |
220 |
280 |
315 |
355 |
400 |
450 |
500 |
Output
ratings
|
Rated
capacity[kVA](*2) |
105 |
128 |
154 |
182 |
221 |
274 |
316 |
396 |
445 |
495 |
584 |
640 |
731 |
| Rated
voltage[V](*3) |
Three-phase,
380, 400V/50Hz, 380, 400, 440, 460V/60Hz (with AVR function) |
| Rated
current[A](*4) |
139 |
168 |
203 |
240 |
290 |
360 |
415 |
520 |
585 |
650 |
740 |
840 |
960 |
| Overload
capability |
120% of
rated current for 1min |
| Rated
frequency[Hz] |
50, 60Hz |
| Input
ratings |
Phases,
voltage,
frequency |
Main power supply |
Three-phase,
380 to 440V, 50Hz
Three-phase, 380 to 480V, 60Hz |
Auxiliary control
power input |
Single
-phase, 380 to 480V, 50/60Hz |
| Voltage/frequency
variations |
Voltage:
+10 to -15% (Voltage unbalance: 2% or less (*8)), Frequency:
+5 to -5% |
| Rated
current[A](*5) |
(with DCR) |
138 |
164 |
201 |
238 |
286 |
357 |
390 |
500 |
559 |
628 |
705 |
789 |
881 |
| (without DCR) |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
| Required
power supply capacity[kVA](*6) |
96 |
114 |
140 |
165 |
199 |
248 |
271 |
347 |
388 |
435 |
489 |
547 |
611 |
Braking
|
Torque[%](*7) |
10 to 15 |
| DC injection
braking |
Starting
frequency: 0.0 to 60.0Hz, Braking time: 0.0 to 30.0s,
Braking level: 0 to 60% |
| DC
REACTOR(DCR) |
Standard |
| Applicable safety standards |
UL508C, C22.2No.14,
EN50178:1997(Applying) |
| Enclosure
(IEC60529) |
IP00 UL
open type |
| oling method |
Fan cooling |
| Weight /
Mass[kg] |
35 |
|
|
|
|
|
|
|
|
|
|
|
|
| (*1) |
Fuji's 4-pole standard motor |
| (*2) |
Rated capacity is calculated by assuming
the output rated voltage as 440V for three-phase 400V
series. |
| (*3) |
Output voltage cannot exceed the power
supply voltage. |
| (*4) |
When setting the carrier frequency (F26)
to 1 kHz, reduce the load to 80% of its rated value. |
| (*5) |
Calculated under Fuji-specified
conditions. |
| (*6) |
Obtained when a DC REACTOR is used. |
| (*7) |
Average braking torque without optional
braking resistor (Varies with the efficiency of the motor.) |
| (*8) |
Voltage unbalance [%] =(Max. voltage [V] -
Min. voltage [V])/(Three-phase average voltage [V])x 67
(IEC61800-3(5.2.3)) |
| |
If this value is 2 to 3%, use an AC