- Rated AC input voltage
| 3-phase
200V |
: |
200 to
230V 50/60Hz |
| Single-phase
200V |
: |
200 to
240V 50/60Hz |
- Allowable variation
| Voltage |
: |
+10%
to -15% (3-phase 200V) |
| Frequency |
: |
+5% to
-5% |
| _ |
Imbalance
rate
in power supply voltage |
: |
2% or
less
(Conforms to
IEC61800-3(5.2.3)) |
- Product range
| 3-phase
200V |
: |
0.1 to
3.7kW |
| Single-phase
200V |
: |
0.1 to
2.2kW |
|


|
|
 |
 |
|

 |

Fuji Compact-size,
Low-noise Inverters
FVR-C11S Series
 |

(Available only in Japan)

| Series |
FVR-C11S |
| Output overload
capability |
150% of rated
current for 1min |
| Braking
torque |
Regenerative braking |
150% or more (0.1,
0.2kW)
100% or more (0.4, 0.75kW)
_50% or
more (1.5kW)
_30% or
more (2.2, 3.7kW) |
| DC injection braking |
Starting
frequency: 3.0Hz (Fixed)
Braking time: 0.1 to 30s
(Adjustable)
Braking voltage: 0 to 100%
(Adjustable) |
| Acceleration time |
0.0 to 60s
(0.0=0.01s) |
| Deceleration time |
0.1 to 60s |
| Multi frequency
control |
4 steps |
| Frequency setting
signal |
0 to 5V DC, 0 to
10V DC, 4 to 20mA |
| Protective functions |
Stall prevention,
overcurrent, undervoltage,
overvoltage, inverter overheating,
external alarm (tripping of external
thermal overload relay), CPU error,
short-circuit, ground fault, surge,
motor overload (tripping of
electronic thermal overload),
inverter overload |
| Alarm relay output |
SPDT contact |
| Enclosure and cooling
method |
Natural cooling
type [IP20]
(0.75kW or less)
Fan cooling type [IP20, except fan]
(1.5kW or more)
|
|
|
 |
 |
|
|
|
|
|
|