400V-SHF-Series(1.5KW~15KW)
|
|
|
Model
|
SHF-1.5K
|
SHF-2.2K
|
SHF-4.0K
|
SHF-5.5K
|
SHF-7.5K
|
SHF-11K
|
SHF-15K
|
|
Applicable
Motor Capacity
|
1.5kW
|
2.2kW
|
4.0kW
|
5.5kW
|
7.5kW
|
11kW
|
15kW
|
|
Output
|
Rated
Capacity (*1)
|
2.8kVA
|
4.2kVA
|
6.2kVA
|
8.7kVA
|
11.8kVA
|
17.3kVA
|
22.2kVA
|
|
Rated
Current (*2)
|
4.0A
|
6.0A
|
9.0A
|
12.6A
|
17A
|
25A
|
32A
|
|
Overload
Current Rating
|
150%
1 min
|
|
Rated
Output Voltage
|
3Φ,
380V at 50Hz, 400V at 50Hz, 460V at 60Hz
|
|
Input
|
Rated
Voltage and Frequency
|
3Φ,
380V to 460V at 50Hz or 60Hz
|
|
Allowable
Fluctuation
|
Voltage:-15%,
+10%
Frequency:±5% Voltage imbalance:
3%max
|
|
Power
Supply Impedance
|
1%
or more (Use the optional reactor if less than
1%)
|
|
Protective
Structure
|
Totally
enclosed(IP20)
|
|
Cooling
Method
|
Forced
air cooling
|
|
Weight
|
4kg
|
4kg
|
4.5kg
|
6.5kg
|
6.5kg
|
7kg
|
10kg
|
|
Control
Function
|
Control
Method
|
V/f
control or sensorless
vector control
|
|
High-Frequency
Carrier
|
Sine
wave PWM (carrier frequency: 1 to 14 kHz) (*3)
|
|
Output
Frequency
Range
|
0.05
to 600 Hz (starting frequency: 0.05 to 20 Hz
variable) (*4)
|
|
Frequency
Setting Resolution
|
Digital
Setting
|
0.01
Hz (0.05 to 600 Hz)
|
|
Analog
Setting
|
0.1%
(10 bits for 0 to 10 V, 4 to 20 mA),
0.2% (9 bits for 0 to 5 V) for maximum output
frequency
|
|
Frequency
Accuracy
|
Digital
Setting
|
±0.01%
of the output frequency (at -10 to +
40°C
)
|
|
Analog
Setting
|
±0.2%
of the maximum output frequency (at 25 ±
10°C
)
(*5)
|
|
DC
Braking
|
Starting
frequency (0.2 to 20 Hz), operation time (0.1 to
10 s), braking force (1 to 10 steps)
|
|
Additional
Functions
|
Restart
after momentary power failure, flying start,
multi-speed operation, frequency jump, auto
alarm recovery,
PID
control operation, simple scheduled operation,
energy-saving operation, torque limiter (for sensorless
vector control only)
|
|
Operation
Function
|
Start/Stop
Setting
|
Operation
panel, serial communication (RS485, RS
232C
),
control circuit terminals
|
|
Frequency
Command Setting
|
Digital
Setting
|
Operation
panel, serial communication (RS485, RS
232C
),
step setting from terminal board
|
|
Analog
Setting
|
2
channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA,
variable resistor (5 kΩ, 0.3 W or more)
|
|
Input
Signals
|
Frequency
command, forward run command, reverse run
command, acceleration/deceleration time setting,
free-run stop/alarm reset, emergency stop,
jogging selection, step frequency setting,
operation signal hold, torque limiter (sensorless
vector control only)
[Digital
input; 8 channels (arbitrary allocation)]
[Analog input; 1 channel for voltage, 1 channel
for current and voltage]
|
|
Output
Signals
|
Contact
Output
|
Alarm
batch and multifunctional contact output (
1C
contact, 250 VAC,
0.3
A
)
|
|
Monitor
Signal
|
Operating,
frequency matching, overload alarm, undervoltage,
overvoltage,
frequency approach
[Open-collector
output: 3 channels (arbitrary allocation),
Analog output: 2 channels]
|
|
LED
Display
|
Frequency,
output current, synchronous rotation, load
factor, output voltage, pressure, line speed (no
units), operating, alarm
|
|
Serial
Communication I/F
|
RS485,
RS
232C
|
|
Function
Extension
|
Software
upgrade by RS
232C
serial communication supported
|
|
External
Power Supply Output
|
24
VDC, 150 mA (control
terminal)
|
|
Protection
Functions
|
Current
limiting, overcurrent
shutoff, motor overload, external thermal alarm,
undervoltage, overvoltage,
momentary power failure, fin overheat, missing
phase
|
|
Warning
Functions
|
Overvoltage
prevention, current limiting during
acceleration/deceleration, brake resistor
overheat, overload, overheating of radiator fins
|
|
Environment
|
Ambient
Temperature
|
-10
to +
50°C
(Remove the top ventilation cover at +
40°C
or higher)
|
|
Storage
Temperature
|
-20
to +
65°C
(*6)
|
|
Ambient
Humidity
|
90%RH
or less (with no condensation)
|
|
Operating
Environment
|
Indoor
at
1,000
m
or lower altitude (No direct sunlight, corrosive
or inflammable gases, oil mist, or dust)
|
| |
|
|
|
|
|
|
|
|
|
|
|
*1 Rated capacity at the output
voltage of 400 V
*2 Rated current should be reduced according to outout
power when input voltage is 400 VAC or higher.
*3 The maximum carrier frequency varies depending on
the capacity of the inverter and the operating status.
*4 The frequency setting range for sensorless vector
control is 1 to 130 Hz for a four-pole motor (depends
on the number of poles).
*5 The maximum output frequency is at 5 V, 10 V, and
20 mA.
*6 This temperature is for short periods, such as
during transportation.
|
|
|